Gas alarm controllerJB-TB-ASD5150

ABUS bus is used for data transmission, which has long transmission distance, strong anti-interference ability and short circuit protection function. It can record 1000 historical gas alarm information, 1000 historical fault information, and 500 system operation information. With RS485 interface, it can communicate with the monitoring system in accordance with the communication protocol, and realize the remote display of alarm information. TF memory card reader (need to be customized), can easily realize the controller history data export and external configuration data import through TF memory card.

Product Certification

Technical parameters

Signal transmissionOperating voltage

ABUS four-bus TBUS Two-bus



AC220V±15%/50HZ


Optional accessoriesWork loss



Spare battery :DC12V/4.5AH 2 batteries


≤10W(without detector)
Undervoltage alarm point and indicating value errorWorking environment

165V±10V ±5%FS


temperature:0℃~ 40℃ humidness:≤93%RH
Alarm threshold and alarm methodCommunication distance
High-limit alarm
Low alarm
Audible and visual alarm
≤1000m(RVSP1.5mm² )
Control outputDisplay mode

Three programmable linkage output

 (contact capacity 5A/DC24V) Or 5A/AC220V)

 pulse output is :500mS after disconnect; 

Continuous output: switching output

5 "high resolution
LCD display
Detection unitDetect gas and bus capacity
%LEL、PPM、%VOL
mg /m³ 、℃、%RH
Combustible gas Toxic and harmful gas

Maximum configuration 4 loops/expandable 

Max 8 loop(64 bits per loop)

System architecture

ENVIRONMENT

GASES